Lennox heat pump error codes

142 codes with causes and test steps, plus 2 settings tables.

CodeMeaningSeverity
10Unknown device detectedHigh
11Missing deviceHigh
12Indoor unit not detectedHigh
13Duplicate comfort sensor IDHigh
14Too many devices of the same typeHigh
15Parameter mismatch detectedLow
20Protocol upgrade requiredHigh
21Incompatible equipment detectedHigh
29Over temperature protection (indoor above 90 F)High
30Low temperature protection (below 40 F)High
31Lost communication with deviceHigh
32Device resettingLow
34Must program unit capacity for deviceHigh
35Incorrect operation of deviceHigh
36Heating when not requestedHigh
37Cooling when not requestedHigh
38Not heating when requestedHigh
39No cooling when requestedHigh
40HP heating lockoutLow
41Device control board replacedLow
610Low room temperature detectedHigh
611High room temperature detectedHigh
700Thermostat temperature sensor problemHigh
701Thermostat temperature above limitHigh
703Thermostat humidity sensor problemMedium
3000Replace filter 1Low
3001Replace filter 2Low
3002Replace humidifier padLow
3003Replace UV bulbLow
3004Maintenance reminderLow
3005PureAir maintenanceLow
65537Missing base (smart hub)High
65538Missing baseLow
65539Thermostat lost connection or internal faultHigh
65540Missing HD wall displayLow
65541Firmware download failedLow
65542Firmware update failedLow
65543Firmware updatedLow
65544More than 8 thermostats in a groupLow
65545Cooling capacity alertMedium
70001IAQ internal sensor faultMedium
70002IAQ internal data faultMedium
70003IAQ side switch in OFF positionHigh
70004Replace Smart IAQ monitorMedium
70501Smart room sensor internal data faultMedium
70502Smart room sensor internal faultMedium
70503Smart room sensor low batteryLow
70504Smart room sensor battery 1%Low
71001Wireless extender internal data faultMedium
71504Suction temperature sensor incorrect readingLow
71505Liquid temperature sensor incorrect readingLow
71506Suction pressure sensor incorrect readingLow
71507Liquid pressure sensor incorrect readingLow
71508Outdoor temperature sensor incorrect readingLow
71509Outdoor coil temperature sensor incorrect readingLow
71510Indoor TXV failureMedium
71512High-pressure switch faultHigh
71513Low-pressure switch faultMedium
71514System low on refrigerant chargeMedium
71515Reversing valve stuckHigh
71516Outdoor fan motor failureHigh
71518Compressor failed to startHigh
71519Incorrect reversing valve modeHigh
71520Blocked liquid lineHigh
71521Outdoor TXV failureHigh
80001IAQ persistent poor air qualityLow
80002Unresponsive wireless device faultLow
80003Lost communication with wireless deviceMedium
80005Unknown wireless device foundMedium
E105Wiring issue / communication problemHigh
E114AC line frequency / distortion problemHigh
E115Low secondary (24 VAC) voltageHigh
E120Unresponsive deviceMedium
E124Thermostat lost communication to smart hubHigh
E125Control hardware problemHigh
E126Control internal communication problemHigh
E132Device control software faultHigh
E180Outdoor temperature sensor problemMedium
E181Outdoor suction pressure transducer faultMedium
E182Outdoor suction temperature sensor faultMedium
E183Outdoor liquid pressure sensor faultMedium
E184Outdoor liquid temperature sensor faultMedium
E345Relay O failureHigh
E400Compressor internal overload trippedMedium
E401Compressor long run cycleLow
E402System pressure tripMedium
E403Compressor short-cyclingMedium
E404Compressor rotor lockedHigh
E405Compressor open circuitHigh
E406Compressor open start circuitHigh
E407Compressor open run circuitHigh
E408Compressor contactor weldedHigh
E409Outdoor control low 24 VACMedium
E410Open low pressure switchLow
E411Low pressure switch strikes lockoutHigh
E412Open high pressure switchLow
E413High pressure switch strikes lockoutHigh
E414High discharge line temperatureMedium
E415High discharge line temperature strikes lockoutHigh
E416Outdoor coil sensor faultyMedium
E417Discharge sensor faultyMedium
E418EIM W output hardware faultMedium
E419EIM W output hardware fault lockoutHigh
E420EIM defrost out of cycleMedium
E421EIM W external miswire faultHigh
E422Compressor top cap switch openMedium
E423Inverter CT circuit fault (inverter code 40)High
E424Liquid line sensor faultyMedium
E426Excessive inverter alarmsHigh
E427Inverter DC peak fault (inverter code 21)High
E428Inverter high main input current (inverter code 22)High
E429Inverter DC link low voltage (inverter code 23)High
E430Inverter compressor startup fail (inverter code 26)High
E431Inverter PFC fault (inverter code 27)High
E432Inverter DC link high voltage (inverter code 28)High
E433Inverter compressor over-current (inverter code 29)High
E434Inverter communication error to main control (inverter code 53)High
E435Inverter EEPROM checksum fault (inverter code 60)High
E436Inverter high heat-sink temperature (inverter code 62)High
E437Inverter heat-sink temperature sensor fault (inverter code 65)High
E438Inverter PFC input over-current (inverter code 73)High
E440Inverter compressor slowdown - high heat-sink temperature (inverter code 13)Low
E441Inverter compressor slowdown - high compressor current (inverter code 14)Low
E442Compressor top cap switch strikes lockoutHigh
E443Unit code to inverter model mismatchHigh
E444Reversing valve relay or solenoid faultHigh
E446Low suction pressure faultHigh
E600Load shed eventLow
E601Low ambient operational lockoutLow
Green & Red alternating FAST flashCoil (defrost) sensor problemHigh
Green & Red alternating SLOW flash5-minute anti-short-cycle delayLow
Green & Red simultaneous FAST flashAmbient (outdoor air) sensor problemMedium
Green FAST flash / Red OFFDischarge sensor lockoutMedium
Green FAST flash / Red ONDischarge line temperature lockoutMedium
Green OFF / Red FAST flashDischarge sensor faultLow
Green OFF / Red OFFNo power to the demand defrost controlMedium
Green OFF / Red ONLow pressure lockoutHigh
Green OFF / Red SLOW flashLow pressure faultMedium
Green ON / Red OFFHigh pressure lockoutHigh
Green ON / Red ONDemand defrost control failureHigh
Green SLOW flash / Red OFFHigh pressure faultMedium
Green SLOW flash / Red ONDischarge line temperature faultLow

Settings and specs

Outdoor unit clearances

Clearances · Lennox EL16KP1

LocationClearance
Service side (one side next to control box)30 in. (762 mm)
One of the other three sides36 in. (914 mm)
One of the remaining two sides12 in. (305 mm)
Last side6 in. (152 mm)
Between two units24 in. (610 mm)
Top48 in. (1219 mm)
Above roof surface (roof mount)6 in. (152 mm) minimum
  • Increase clearances where snow/ice can fall on the unit or air can recirculate (decks, tight spaces).
  • Wind barrier, if used, 24 in. (610 mm) from the unit.

Source: Lennox EL16KP1 Unit Information 100195 (03-2025), Installation Clearances p.6, Roof Mounting p.14

Outdoor unit clearances

Clearances · Lennox ML14KP1

LocationClearance
Service side (one side next to control box)24 in. (610 mm)
One of the other three sides36 in. (914 mm)
One of the remaining two sides12 in. (305 mm)
Last side6 in. (152 mm)
Top48 in. (1219 mm)
Multi-unit, between units12 in. (305 mm) minimum [18 in. (457 mm) recommended] or 24 in. (610 mm) depending on layout
Multi-unit service side24 in. (610 mm) recommended
Above roof surface (roof mount)6 in. (152 mm) minimum
  • Multi-unit spacing (A/B) depends on single row, wall or multiple rows layout - see figure on p.7.
  • Increase clearances where snow/ice can fall on the unit or air can recirculate.

Source: Lennox ML14KP1 Unit Information 100108 (03-2026), Installation Clearances p.7, Roof Mounting p.14

Models covered

EL16KP1-018EL16KP1-024EL16KP1-030EL16KP1-036EL16KP1-042EL16KP1-048EL16KP1-060ML14KP1-018ML14KP1-024ML14KP1-030ML14KP1-036ML14KP1-042ML14KP1-048ML14KP1-060

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.