Lennox · Heat pump
Green ON / Red OFF High pressure lockout
What the control is telling you
The high pressure switch tripped 5 times (5 strikes) and the control locked out the compressor.
Applies to: Lennox EL16KP1 (Elite) and ML14KP1 (Merit) R-454B heat pumps, sizes -018 to -060, demand defrost control A108 (CMC1)
Likely causes
- Restricted airflow over the indoor or outdoor coil (dirty coil, filter, blocked fan)
- Wrong refrigerant charge
- Wrong metering device installed or expansion valve not working properly
- Pressure switch or sensor mounted wrong or loose connection
Test and repair steps
- Clean the outdoor coil and make sure the outdoor fan runs at the right speed and current.
- In heating, check indoor airflow (dirty filter, closed registers, blower speed) - the indoor coil is the condenser.
- Check the charge with the subcooling method; an overcharge raises head pressure.
- Compare operating pressures with the Normal Operating Pressures table for the unit size.
- Confirm the correct indoor expansion valve is installed and working.
- Check the high pressure switch (S4, opens at 590 +/- 15 psig) wiring at HS-PS; make sure pressure switches and sensors are tight on the system.
- To clear a 5-strike lockout after the repair, place a jumper on the TEST pins (P1) or cycle 24 VAC power to the defrost control; then put the jumper back on the desired setting.
Settings for these units
- Outdoor unit clearances · Lennox EL16KP1
- Outdoor unit clearances · Lennox ML14KP1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL16KP1 Unit Information 100195 / ML14KP1 Unit Information 100108, Table 4 Demand Defrost Control (A108) Diagnostic LEDs, p.32. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.