Lennox · Heat pump
Green OFF / Red SLOW flash Low pressure fault
What the control is telling you
The low pressure switch (S87, opens at 25 +/- 5 psig, closes at 40 +/- 5 psig) opened and the control stopped the compressor and counted one strike. It is ignored during defrost, for 90 s after defrost, for 90 s after compressor start in TEST mode, and for 10 minutes of compressor run when ambient is below 15°F. Two LP trips in a row in heating start a defrost.
Applies to: Lennox EL16KP1 (Elite) and ML14KP1 (Merit) R-454B heat pumps, sizes -018 to -060, demand defrost control A108 (CMC1)
Likely causes
- Restricted airflow over the indoor or outdoor coil (dirty coil, filter, blocked fan)
- Wrong refrigerant charge
- Wrong metering device installed or expansion valve not working properly
- Pressure switch or sensor mounted wrong or loose connection
Test and repair steps
- Clear any blockage or restriction on the indoor and outdoor coils and fans; check the filter.
- Check indoor and outdoor fan motor current draw against the nameplate.
- Check the charge with the subcooling method and compare with the unit charging label / matchup table.
- Compare operating pressures with the Normal Operating Pressures table for the unit size.
- Confirm the correct indoor expansion valve is installed and working.
- Make sure the pressure switches and sensors are tight on the system so there are no leaks or false readings.
Settings for these units
- Outdoor unit clearances · Lennox EL16KP1
- Outdoor unit clearances · Lennox ML14KP1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL16KP1 Unit Information 100195 / ML14KP1 Unit Information 100108, Table 4 Demand Defrost Control (A108) Diagnostic LEDs, p.32. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.