Lennox · Heat pump
E443 Unit code to inverter model mismatch
What the control is telling you
The variable capacity outdoor control has the wrong unit size code for its inverter. S30/S40 thermostat alert code 443 (shown as E443 on the unit control display).
Applies to: Lennox communicating heat pumps incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- Wrong unit size code
- Replacement inverter does not match unit size
Test and repair steps
- Set the correct outdoor unit size code (configuration guide / installation instructions).
- If the inverter was replaced, verify its model matches the unit size.
- Remove the thermostat from the system while powering up and reprogramming.
- Clears after correct match following power reset.
Settings for these units
- Outdoor unit clearances · Lennox EL16KP1
- Outdoor unit clearances · Lennox ML14KP1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.43. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.