Lennox · Heat pump
E438 Inverter PFC input over-current (inverter code 73)
What the control is telling you
PFC over-current detected; inverter resets after three minutes. 10 times in a rolling 60 minutes = lockout. Inverter LED flash code 73 (red 7 flashes, green 3 flashes). S30/S40 thermostat alert code 438 (shown as E438 on the unit control display).
Applies to: Lennox communicating heat pumps incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- High load
- High pressure
- Outdoor fan failure
Test and repair steps
- Look at the thermostat and outdoor control for other alert codes or high pressure trips.
- Check outdoor fan operation.
- Service urgent clears when the inverter is power cycled.
- Check inverter LEDs flash code 73 = red 7 flashes, green 3 flashes. Normal inverter LEDs with no fault: red ON, green OFF.
Settings for these units
- Outdoor unit clearances · Lennox EL16KP1
- Outdoor unit clearances · Lennox ML14KP1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.41. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.