Lennox · Heat pump
14 Too many devices of the same type
What the control is telling you
More than one thermostat, indoor unit or outdoor unit is connected to the system. S30/S40 thermostat alert code 14.
Applies to: Lennox communicating heat pumps incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- Duplicate equipment or wiring error on the communication bus
Test and repair steps
- Check the wiring and remove the duplicate equipment.
- S30 go to Menu > Settings > Advanced Settings, open View Dealer Control Center, then pick Equipment > Reset All Equipment. The thermostat will find every Lennox communicating device again.
- S40 go to Menu > Settings > Advanced Settings, open View Service Support Center, then Equipment Setting > Reset and pick Reset HVAC Equipment.
- Clears automatically once fixed.
Settings for these units
- Outdoor unit clearances · Lennox EL16KP1
- Outdoor unit clearances · Lennox ML14KP1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.9. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.