Lennox · Heat pump

13 Duplicate comfort sensor ID

High severity

What the control is telling you

The thermostat found more than one outdoor unit, indoor unit or thermostat; it shows 'Too Many Devices of the Same Type'. S30/S40 thermostat alert code 13.

Applies to: Lennox communicating heat pumps incl. variable-capacity inverter units in S30/S40 smart thermostat systems

Likely causes

  • Duplicate equipment or wiring error on the communication bus

Test and repair steps

  1. Check the wiring and remove the duplicate equipment.
  2. S30 go to Menu > Settings > Advanced Settings, open View Dealer Control Center, then pick Equipment > Reset All Equipment. The thermostat will find every Lennox communicating device again.
  3. S40 go to Menu > Settings > Advanced Settings, open View Service Support Center, then Equipment Setting > Reset and pick Reset HVAC Equipment.
  4. Clears automatically once fixed.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.9. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.