Lennox · Heat pump
E402 System pressure trip
What the control is telling you
Compressor overload, or suction or discharge pressure outside its limits. S30/S40 alert code 402; unit control shows E402.
Applies to: Lennox communicating heat pumps incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- High or low refrigerant charge
- Dirty coil or failed fan
- Restriction
Test and repair steps
- Check discharge and suction pressures.
- Check outdoor coil, fan and indoor airflow.
- Clears after four consecutive normal compressor run cycles.
Settings for these units
- Outdoor unit clearances · Lennox EL16KP1
- Outdoor unit clearances · Lennox ML14KP1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.29. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.