Lennox · Heat pump

39 No cooling when requested

High severity

What the control is telling you

Cooling could not be turned on for more than 45 minutes; the system goes off-line for 60 minutes, then tries to restart. S30/S40 thermostat alert code 39.

Applies to: Lennox communicating heat pumps incl. variable-capacity inverter units in S30/S40 smart thermostat systems

Likely causes

  • Outdoor unit fault or lockout
  • Wiring or communication problem

Test and repair steps

  1. Run diagnostics and compare with what the equipment actually does (S30: Dealer Control Center > Diagnostics > Start Diagnostics; S40: Service Support Center > Diagnostics > Select All > Start).
  2. Look for other alert codes that block cooling.
  3. Check all cooling equipment for the cause.
  4. Cycle power. Clears automatically once fixed.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.12. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.