Lennox · Heat pump

80001 IAQ persistent poor air quality

Low severity

What the control is telling you

Poor indoor air quality persists (dealer information). S30/S40 thermostat alert code 80001.

Applies to: Lennox communicating heat pumps incl. variable-capacity inverter units in S30/S40 smart thermostat systems

Likely causes

  • IAQ equipment off or not working
  • Dirty filters
  • UV lamp out

Test and repair steps

  1. Cycle power to the device.
  2. Check all IAQ equipment is powered and working.
  3. Check HC air filters, PureAir / PureAir S filter and UV lamp, ERV/HRV filter and germicidal UV lamp; replace as needed.
  4. Replace the device if nothing else fixes it.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.51. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.