Lennox · Heat pump
E404 Compressor rotor locked
What the control is telling you
The compressor rotor is locked up. S30/S40 thermostat alert code 404 (shown as E404 on the unit control display).
Applies to: Lennox communicating heat pumps incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- Shorted run capacitor
- Seized bearings
- Excessive liquid refrigerant in compressor
Test and repair steps
- Check the run capacitor.
- Check for liquid floodback / overcharge.
- A hard start kit may be needed.
- Clears after four consecutive normal run cycles or power reset.
Settings for these units
- Outdoor unit clearances · Lennox EL16KP1
- Outdoor unit clearances · Lennox ML14KP1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.29. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.