Lennox · Heat pump

E418 EIM W output hardware fault

Medium severity

What the control is telling you

Power on the W terminal during cooling. S30/S40 alert code 418; unit control shows E418.

Applies to: Lennox communicating heat pumps incl. variable-capacity inverter units in S30/S40 smart thermostat systems

Likely causes

  • Stuck relay on the control
  • External wiring back-feeding W

Test and repair steps

  1. Disconnect all wires from W.
  2. If 24 VAC is still on W, the relay is stuck (replace control).
  3. If voltage disappears, check the wires connected to W.
  4. Clears when the fault signal is removed.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.31. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.