Lennox · Heat pump
E180 Outdoor temperature sensor problem
What the control is telling you
No good reading from the outdoor sensor (the one in the outdoor unit, or the optional one on the indoor unit). S30/S40 alert code 180; unit control shows E180.
Applies to: Lennox communicating heat pumps incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- Open or shorted sensor or wiring
- Sensor out of range
Test and repair steps
- Compare sensor resistance with the temperature/resistance chart in the unit installation instructions.
- Replace the sensor pack or stand-alone outdoor sensor.
- Sensors are detected at configuration and shown as installed in the About screen; reconfigure if a sensor was removed.
- Clears on configuration or when normal readings return.
Settings for these units
- Outdoor unit clearances · Lennox EL16KP1
- Outdoor unit clearances · Lennox ML14KP1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.18. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.