Midea heat pump error codes

34 codes with causes and test steps, plus 1 settings tables.

CodeMeaningSeverity
EC5CHigh pressure sensor failureMedium
EC07Outdoor DC fan motor fault / speed out of controlHigh
EC50outdoor temperature sensor faultMedium
EC51Outdoor EEPROM errorHigh
EC52condenser coil temperature sensor faultMedium
EC53outdoor ambient temperature sensor faultMedium
EC54Discharge temperature sensor (TP) open/shortMedium
EC57refrigerant pipe temperature sensor faultMedium
EC71Outdoor DC fan motor over-currentHigh
EC72Outdoor DC fan motor lack-phaseHigh
EL01Indoor/outdoor communication errorHigh
EL16Main board to transit board communication errorHigh
LC06Inverter module (IPM) high temperature protectionHigh
PC00Inverter module (IPM) protectionHigh
PC0ACondenser high temperature protectionMedium
PC0FPFC module protectionHigh
PC0LOutdoor unit low-temperature protectionLow
PC02Compressor top temperature protectionHigh
PC06Compressor discharge temperature protectionHigh
PC08Outdoor over-current protectionHigh
PC10Outdoor low AC voltage protectionMedium
PC11Outdoor DC bus high voltage protectionHigh
PC12DC bus high voltage protection / 341 MCE errorHigh
PC30System high pressure protectionHigh
PC31System low pressure protectionHigh
PC40Main chip to compressor-driver chip communication errorHigh
PC42Compressor start failureHigh
PC43Compressor lack-phase protectionHigh
PC44Outdoor unit zero-speed protectionHigh
PC45Outdoor IR chip drive failureHigh
PC46Compressor speed out of controlHigh
PC49Compressor over-current failureHigh
PH90Evaporator high temperature protectionMedium
PH91Evaporator low temperature protectionMedium

Settings and specs

Outdoor unit minimum clearances

Clearances · Midea DLCURA ducted single-zone inverter heat pump (outdoor)

SideMinimum
A - top24 in. (610 mm)
B - right side (service side)24 in. (610 mm)
C - front (air outlet)24 in. (610 mm)
D - left side4 in. (101 mm)
E - rear (air inlet)4 in. (101 mm)
Above max snow depth2 in. (50 mm)
  • Side letters taken from Fig. 8 drawing.
  • Units facing each other: 59 in. (150 cm) or more; do not blow into another unit's inlet.
  • Do not bury more than 36 in. of line set; buried lines need a 6 in. rise at the valves.

Source: Midea DLCURA Installation Instructions (Catalog No. DLCURA-03SI, 12/22), Table 5 Clearance Dimensions and Fig. 8-9, PDF p.10 (printed p.8); burial caution PDF p.4

Models covered

DLCURAH18AAKDLCURAH18ABKDLCURAH24AAKDLCURAH24ABKDLCURAH30AAKDLCURAH30ABKDLCURAH36AAKDLCURAH36ABKDLCURAH48AAKDLCURAH48ABKDLCURAH60AAKDLCURAH60ABK

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.