PC10 Outdoor low AC voltage protection

Medium severity Midea DLCURA ducted single-zone inverter heat pump (outdoor)

What the control is telling you

Incoming AC voltage is too low.

Applies to: DLCURAH18-60 AAK/ABK single-zone heat pump outdoor units (18K-60K, regular and High Heat)

Likely causes

  • Supply voltage below 187 V
  • Loose connection at disconnect or terminal block
  • Undersized wire

Test and repair steps

  1. Warning: Live voltage testing - use proper PPE.
  2. Measure voltage at the outdoor terminal block with the unit running; acceptable range is 187-253 V.
  3. Tighten connections at the disconnect and terminal block.
  4. Check wire size and breaker per the electrical data (MCA/MOCP).
  5. Have the utility or electrician correct low supply voltage.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Midea/Carrier DLCURA Installation Instructions (Catalog DLCURA-03SI), Table 11 Outdoor Unit Diagnostic Codes, p.19. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.