Midea · Heat pump
PC11 Outdoor DC bus high voltage protection
What the control is telling you
The outdoor main board's DC bus voltage is too high.
Applies to: DLCURAH18-60 AAK/ABK single-zone heat pump outdoor units (18K-60K, regular and High Heat)
Likely causes
- Supply voltage above 253 V or surges
- Board fault
Test and repair steps
- Warning: Turn off and lock out power at the outdoor disconnect and wait for the inverter capacitors to discharge before touching the outdoor board or compressor wiring.
- Measure supply voltage; it must not exceed 253 V.
- Check for voltage spikes/surges on the supply.
- If supply is correct, replace the outdoor main board.
Settings for these units
- Outdoor unit minimum clearances · Midea DLCURA ducted single-zone inverter heat pump (outdoor)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Midea/Carrier DLCURA Installation Instructions (Catalog DLCURA-03SI), Table 11 Outdoor Unit Diagnostic Codes, p.19. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.