Midea · Heat pump
PC06 Compressor discharge temperature protection
What the control is telling you
Discharge temperature is too high, so the compressor is stopped to protect it.
Applies to: DLCURAH18-60 AAK/ABK single-zone heat pump outdoor units (18K-60K, regular and High Heat)
Likely causes
- Low refrigerant charge / leak
- Refrigerant restriction
- Poor outdoor airflow
- Faulty TP sensor reading high
Test and repair steps
- Warning: Turn off and lock out power at the outdoor disconnect and wait for the inverter capacitors to discharge before touching the outdoor board or compressor wiring.
- Check charge and leak-test the system.
- Check the outdoor coil and fan.
- Check the line set for kinks or restrictions; check line length vs. charge (18K: 24.6 ft before adding charge, 0.69 oz/ft beyond).
- Check the TP sensor is attached to the discharge line and reads correctly.
Settings for these units
- Outdoor unit minimum clearances · Midea DLCURA ducted single-zone inverter heat pump (outdoor)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Midea/Carrier DLCURA Installation Instructions (Catalog DLCURA-03SI), Table 11 Outdoor Unit Diagnostic Codes, p.19. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.