41 Freeze protection / outdoor air temperature sensor fault
What the control is telling you
The freeze protection (outside air) thermistor is open, shorted or disconnected. KB units will not fire; VC units and outdoor units keep running while flashing 41 alternately with the set point.
Applies to: SENSEI and Non-SENSEI Series (external/outdoor models); all SENSEI RX/CX Series models
Likely causes
- Loose, broken or damaged sensor harness
- Sensor unplugged, cut or shorted
- Sensor covered by insulation instead of exposed to outside air
- Sensor resistance out of spec
- Temperature controller wired to the wrong terminals
Test and repair steps
- Inspect the sensor harness from sensor to PC board for loose, broken or damaged connections.
- Make sure the sensor is exposed to outside air and not buried in insulation.
- With a meter set for 20K ohms, measure across the sensor plug; resistance should drop when warmed and rise when cooled.
- Typical values 11.4–14K ohms at 59°F, 6.4–7.8K at 86°F, 3.6–4.5K at 113°F, 2.2–2.7K at 140°F, 0.6–0.8K at 221°F.
- Note An open sensor on outdoor units (all RX/CX units) lets the heater keep running while flashing 41; the code clears once the issue is fixed.
- Confirm the temperature controller is wired to the connection point shown in the Installation and Operation manual; if it is connected anywhere else, disconnect it immediately and rewire correctly.
Settings for these units
- RSC supply connection sizes · SENSEI
- RSC water quality limits · SENSEI
- RSC clearances to combustibles · SENSEI
- RSC temperature settings available · SENSEI
- RX supply connection sizes · SENSEI RX/CX
- RX water quality limits · SENSEI RX/CX
- RX water treatment and flushing by hardness · SENSEI RX/CX
- RX clearances to combustibles · SENSEI RX/CX
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.44. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.