Rinnai · Tankless water heater
38 Exhaust gas temperature sensor (CO sensor on RH180)
What the control is telling you
The exhaust gas temperature sensor reports a fault or abnormal flue conditions; on RH180 models this code relates to the CO sensor and venting/combustion air problems.
Applies to: SENSEI Series; SENSEI RX/CX Series; Non-SENSEI Series; RH180 (CO sensor steps)
Likely causes
- Loose or damaged sensor wiring, or sensor out of spec
- Wrong gas type or improper gas conversion
- Incorrect parameters/DIP switches or manifold gas pressures
- Debris in burner, manifold or heat exchanger fins
- Venting clearances, lengths or materials not per spec
- Insufficient combustion air (RH180)
- Restricted fan wheel, housing or air duct (RH180)
- Failed CO sensor or PC board (RH180)
Test and repair steps
- Inspect sensor wiring at sensor and PC board. Remove sensor and test at 20K ohms: 11.4–14K at 59°F, 6.4–7.8K at 86°F, 3.6–4.5K at 113°F, 2.2–2.7K at 140°F, 0.6–0.8K at 221°F; should fall when warmed.
- If readings are good, reinstall the sensor in the exhaust port and run water to fire the unit; continue if code 38 returns.
- Confirm gas type matches the rating plate, any gas conversion was done per the Gas Conversion manual, clearances are met, and parameters/DIP switches suit the site.
- Warning: Only technicians qualified on gas systems should continue. Verify forced low/high fire manifold pressures with a manometer per the Technical Data Sheet.
- Warning: Shut off gas and water first. Inspect burner manifold, burners and heat exchanger copper fins for debris; confirm venting clearances and lengths. If code 38 remains, replace the sensor.
- RH180 Confirm 4 in. B-Vent was used and the full vent system is properly installed, seated and sealed with correct clearances.
- RH180 Check combustion air for all gas appliances in the space; if the unit runs with a door open, recalculate combustion air requirements.
- RH180 Set altitude DIP switches 2 and 3: 0–2,000 ft both OFF; 2,001–5,400 ft SW2 OFF, SW3 ON.
- RH180 (WARNING, qualified gas techs only): Inlet gas NG 4–10.5 in. w.c., LP 8–13.5 in. w.c. with all appliances on high fire; forced low NG 1.10/LP 1.23, forced high NG 2.8/LP 3.0 in. w.c.
- RH180 (CAUTION, power off) Remove the fan and inspect wheel, housing and air duct for restrictions; reinstall, restore power and test.
- RH180 (WARNING, power/gas/water off) Check manifold orifices, burner chamber and HX fins for debris; blow out with 120 psi air or replace the heat exchanger.
- Caution: Wear safety glasses and a mask when blowing out the burner.
- RH180 Review the RH180 steps under Codes 05 and 10. Check CO sensor at C1, Red–Black pins 1–5: 1.9–2.1 VDC normal, 2.5–3 VDC during combustion.
- RH180 Before replacing the CO sensor, ventilate the room, cycle power, wait 30 minutes and retry. If unresolved, replace the CO sensor and PC board.
Settings for these units
- RSC supply connection sizes · SENSEI
- RSC water quality limits · SENSEI
- RSC clearances to combustibles · SENSEI
- RSC temperature settings available · SENSEI
- RX supply connection sizes · SENSEI RX/CX
- RX water quality limits · SENSEI RX/CX
- RX water treatment and flushing by hardness · SENSEI RX/CX
- RX clearances to combustibles · SENSEI RX/CX
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.42–43. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.