ICP · Furnace

1+5 Blower motor lockout

High severity ICP (F/G)9MAE Modulating Furnace

What the control is telling you

Blower did not reach 250 RPM or did not communicate within 30 seconds after start-up in two heat cycles in a row. Auto-resets after 3 hours. Troubleshoot as code 4+1.

Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)

Likely causes

  • Rubbing or loose blower wheel
  • Wiring fault between control and blower motor
  • Failed blower control module / motor
  • Failed furnace control

Test and repair steps

  1. Warning: Turn power off before touching the blower or its connectors.
  2. Follow the 4+1 procedure check the wheel turns freely and is tight on the shaft.
  3. Check 115 VAC at PL14-5/PL14-4, 12 VDC and 5 VDC on PL13 and PL3 as in code 4+1.
  4. Repair open wires/bad terminals or replace the blower control module or furnace control as indicated.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Figure 16 Troubleshooting Chart, p.34. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.