ICP · Furnace
2 Pressure switch did not open
What the control is telling you
A pressure switch was still closed when it should be open (before the inducer starts).
Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)
Likely causes
- Obstructed pressure switch tube
- Pressure switch stuck closed
Test and repair steps
- Check pressure tubes for blockage or water; clean and shake out.
- Do not blow into a tube while it is connected to the pressure switch.
- Check the switch opens with the inducer off (ohmmeter); replace if stuck closed.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Figure 16 Troubleshooting Chart, p.34. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.