ICP · Furnace

1+2 Blower on after power-up (normal)

Low severity ICP (F/G)9MAE Modulating Furnace

What the control is telling you

Normal: blower runs 90 seconds when power is restored during a heat call, or when W/W1 opens during the blower on-delay. Not a fault.

Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)

Likely causes

  • Power interrupted during a call for heat
  • Thermostat W/W1 opened during blower on-delay

Test and repair steps

  1. Wait 90 seconds - the LED should return to heartbeat.
  2. If it repeats often, look for loose 115 V or 24 V supply connections causing power interruptions.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Figure 16 Troubleshooting Chart, p.34. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.