EEL Igniter relay / igniter circuit fault
What the control is telling you
The control detected a problem in the igniter circuit: wiring, a shorted or improperly connected igniter, poor ground, or a failed igniter relay on the board.
Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready
Likely causes
- Wiring problem between control and igniter
- Shorted or improperly connected igniter
- Poor unit ground
- Igniter relay fault on the integrated control
Test and repair steps
- Check and correct the wiring and plug between the integrated control and the igniter.
- Ohm the igniter at room temperature (37-68 ohms silicon nitride; 30-300 ohms carbide mini igniter on 80% models); replace a shorted igniter.
- Verify the unit ground wire runs back to the panel and the ground connection is tight.
- During igniter warm-up, check for 115 VAC output at the control's igniter terminals; no output with a good igniter and wiring = replace the control board.
Settings for these units
- Normal status displays (7-segment) · Daikin DR96TN/DD96TN
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.