Daikin · Furnace
EEJ Inducer relay error
What the control is telling you
The control detected a fault in its inducer relay circuit. The furnace will not operate.
Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready
Likely causes
- Failed inducer relay on the integrated control board
Test and repair steps
- Cycle power and retry to confirm the code returns.
- Check for 115 VAC from the control to the inducer during a heat call; with good wiring and no output, replace the integrated control board.
- If the inducer gets voltage but does not run, test the inducer motor windings (continuity between leads, none to ground) instead.
Settings for these units
- Normal status displays (7-segment) · Daikin DR96TN/DD96TN
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.