Daikin · Furnace

EEb External gas valve error - valve not energized when it should be

High severity Daikin DR96TN/DD96TN

What the control is telling you

During a heat call the control does not see voltage at the gas valve when it should. Flowcharts call this code Eb. Note: the wiring diagram legend labels this code 'Internal Gas Valve Error' while the troubleshooting chart and flowchart say external (valve not powered) - follow the chart.

Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready

Likely causes

  • Miswired or loose gas valve harness
  • Gas valve coil shorted to ground
  • Open front cover pressure switch on 90% models (it is in series with the valve)
  • Failed control board output

Test and repair steps

  1. Check the gas valve wiring against the wiring diagram and correct any miswiring.
  2. Remove the wires from the gas valve and check the valve for a short to ground; replace a shorted valve.
  3. With a call for heat and the igniter on, check for 24 VAC between the valve wires (MV/MVL and common) at the harness connector on the control board.
  4. Voltage at the board but not at the valve: check the harness and, on 90% models, the front cover pressure switch in series with the valve.
  5. No voltage at the board output during trial for ignition: replace the integrated control board.
  6. If the valve voltage does not match transformer voltage, look for a grounding problem.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29; Error Code (Eb & EC) flowchart p.37; wiring diagram legend p.38. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.