18 Gas valve air/fuel adjustment limit reached
What the control is telling you
The Smart-Sense gas valve has hit its rich or lean air/fuel adjustment limit for the selected gas type, which should not happen in normal operation.
Applies to: SENSEI RX/CX Series
Likely causes
- Wrong gas being supplied to the unit
- Parameter 10 (Gas Type) set incorrectly
- Incorrect gas valve parameters entered
- Flame rod wire disconnected or damaged
Test and repair steps
- Confirm the correct gas (natural gas or propane) is being supplied.
- Check Parameter 10 (A = Natural Gas, B = Propane). It can only be changed within 20 minutes after a power reset.
- Verify or re-enter the gas valve parameters per 'Enter Gas Valve Parameters' in the Gas Valve Replacement Instructions (100000855).
- Confirm the flame rod wire is connected and undamaged.
Settings for these units
- RX supply connection sizes · SENSEI RX/CX
- RX water quality limits · SENSEI RX/CX
- RX water treatment and flushing by hardness · SENSEI RX/CX
- RX clearances to combustibles · SENSEI RX/CX
- RX temperature settings available · SENSEI RX/CX
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.30. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.