Rinnai · Tankless water heater
07 Circulation flow rate below 2.1 GPM
What the control is telling you
On the RH180 hybrid, the water circulating through the unit has dropped below 2.1 GPM.
Applies to: RH180 hybrid tank-tankless (non-SENSEI) only
Likely causes
- No power to the unit
- Water supply off, or supply pressure under 30 PSI
- Pump not running, or pump wiring loose/damaged
- Clogged inlet water filter
- Scale build-up in the heat exchanger
Test and repair steps
- Make sure the unit has power.
- Make sure the water supply is on and pressure is at least 30 PSI.
- Check that the pump runs, and check its wiring harness for loose, damaged or broken connections.
- Drain the tank and clean the inlet water filter.
- Flush the heat exchanger to remove scale, following the flushing procedure in the Installation and Operation Manual.
Settings for these units
- RSC supply connection sizes · SENSEI
- RSC water quality limits · SENSEI
- RSC clearances to combustibles · SENSEI
- RSC temperature settings available · SENSEI
- RX supply connection sizes · SENSEI RX/CX
- RX water quality limits · SENSEI RX/CX
- RX water treatment and flushing by hardness · SENSEI RX/CX
- RX clearances to combustibles · SENSEI RX/CX
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.11. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.