220 Gas valve position not detected (reed switch)
What the control is telling you
The reed switches (sensors) cannot detect the correct position of the gas valve.
Applies to: I-Series Plus boilers — 150K BTU and smaller (Combi and Solo)
Likely causes
- Reed switch mispositioned on the front of the gas valve
- Incorrect gas valve parameters
- Loose, damaged or wet wiring between reed switch and PC Board
Test and repair steps
- Confirm the reed switch on the front of the gas valve is seated in the proper location (see diagrams in the source manual, p.15).
- Verify the gas valve parameters, or re-enter them per 'Enter Gas Valve Values from Integrated Controller' in the Gas Valve Assembly Replacement Instructions (800000253).
- Check the wiring from the reed switch to the PC Board for loose, damaged or wet connections.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting I-Series Plus Boiler Diagnostic Codes (800000375), p.14–15. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.