Rinnai · Combi boiler
210 Data transfer error
What the control is telling you
Indicates a problem with transferring PC Board data, typically after a PC Board replacement.
Applies to: I-Series Plus boilers — 150K BTU and smaller (Combi and Solo)
Likely causes
- Incomplete data transfer after PC Board replacement
- Parameters not programmed for the boiler model
- Data transfer instructions not followed
Test and repair steps
- If the PC Board was replaced, make sure the data transfer finished.
- Confirm all parameters are programmed correctly for this boiler model.
- Confirm the data transfer instructions supplied with the new board were followed.
- If transfer failed, enter the gas valve values manually per 'Enter Gas Valve Values from Integrated Controller' in the Gas Valve Assembly Replacement Instructions (800000253).
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting I-Series Plus Boiler Diagnostic Codes (800000375), p.13. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.