Rheem · Furnace
6 blinks Line and neutral reversed
What the control is telling you
The STATUS LED on the furnace control flashes 6 times: the control sees hot (L1) and neutral swapped on the 115 V supply. With reversed polarity the control may not be able to prove flame, so the furnace can light and drop out or lock out.
Applies to: Rheem RGRM upflow and RGTM downflow/horizontal two-stage condensing gas furnaces (90 Plus)
Likely causes
- L1 (hot) and neutral swapped at the furnace junction box or in the supply wiring
- Wrong polarity at a receptacle or plug-in cord feeding the furnace
- Poor or missing ground at the furnace or control
Test and repair steps
- Warning: Turn off power at the disconnect before opening the junction box; line voltage is present inside.
- At the furnace junction box confirm the black supply wire goes to L1 (hot) and the white to neutral, and that the ground wire is connected.
- With power on, measure L1 to neutral should read about 115 V, neutral to ground close to 0 V, L1 to ground about 115 V. If neutral to ground reads line voltage, the wires are reversed.
- If the furnace is fed from a receptacle, check the receptacle for reversed polarity and correct it.
- Correct the wiring, restore power and confirm the STATUS LED returns to steady on and the burners stay lit through a full heat call.
Settings for these units
- Filter sizes · Rheem RGRM/RGTM 90 Plus
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem RGRM/RGTM Installation Instructions 92-24161-84-01 (Nature Air RGRM-04*MAES on ManualsLib), Troubleshooting - STATUS LED codes, p.53; Electrical Wiring polarity note. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.