What the control is telling you
Gas heat is locked out for 1 hour, then the control retries automatically. On 802P and R95P, 10 alternates with the code that caused it (11, 13, 14, 61; R95P also 59). On RGPE/RGLE the thermostat shows IGN 1 HR RTRY plus Call For Service / CHECK FURNACE. R95P manual inconsistency: its flowchart says lockout shows as '1'.
Applies to: 802P/80MDP (802PA050-150); R95P (R95PA040-115); RGPE/RGLE 2-stage 80+
Likely causes
- Repeated failed ignition (4 trials)
- Flame lost 5 times in one heat call
- Unexpected flame
- Dead blower - main limit open more than 150 seconds (802P, R95P)
- Unexpected voltage on the gas valve circuit that clears when the inducer stops (802P, R95P)
- R95P: water sensed again within 5 minutes of the next heat attempt in the same call
Test and repair steps
- Read the code shown with 10 (or the fault buffer) and troubleshoot that fault first.
- 802P / R95P on power-up the 3 most recent faults less than one week old flash newest to oldest.
- RGPE/RGLE on power reset the last five codes show newest first.
- Lockouts clear when the fault is fixed and power is cycled; a soft lockout can also be cleared by removing the heat call for more than 2 but less than 20 seconds.
- RGPE/RGLE shut off main power, wait 30 seconds and restore, or remove and re-establish the heat call.
- While locked out, cooling and fan calls still run but the display shows the lockout code (802P, R95P).
- If nothing is done the lockout resets itself after 1 hour.
Settings for these units
- Clearance to combustibles (all models) · R95P
- Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE
- Reduced clearance to combustibles, upflow/horizontal (Fig. 4) · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)
- Reduced clearance to combustibles (Fig. 3 and 4) · RGPE/RGLE
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: 802P: 92-24161-146-02, Diagnostics and Fault Codes / Lockout, p.40-41; R95P: Lockout section, p.88 (PDF p.92); RGPE/RGLE: Table 16 p.49 / Table 20; Fig. 45 p.64. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.