Noritz · Tankless water heater

91 Gas conversion not done correctly

Critical severity Noritz EZNoritz NRCR

What the control is telling you

EZ/NRCR: the unit's gas conversion was not completed correctly.

Applies to: Noritz EZ111/EZ98/EZ71 and NRCR111/NRCR92

Likely causes

  • LP orifice installed but gas type not changed in the app/display (or the reverse)
  • Gas conversion connector missing (NG to LP)
  • Wrong conversion kit

Test and repair steps

  1. Warning: Do not run the unit on LP until conversion is complete and verified; exhaust odor or burning eyes can mean a bad conversion.
  2. Confirm the kit CK-85 = NG to LP (includes the gas conversion connector), CK-84 = LP to NG.
  3. Check the orifice, o-rings and emission port cap gasket were replaced.
  4. Plug in the LP conversion connector and set the gas type in the EZ Start Plus app (Unit Setting > Convert Gas Type) or the display.
  5. Check inlet gas pressure and offset pressure at the gas valve with a digital manometer, and check combustion with a gas analyzer.
  6. Leak test, then fill out and attach the gas conversion sticker.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Noritz EZ/NRCR Owner's Guide (Rev. 10-25), Checking for error conditions / Gas conversion, p.31, 33; Noritz NRCR Pro training (NRCR92/NRCR111, Printable V3), Field gas conversion, p.3-6. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.