Noritz · Tankless water heater

901 Combustion abnormality (sub-code of 90)

High severity Noritz EZNoritz NRCR

What the control is telling you

EZ/NRCR owner's guide lists 901 and 902 with 90: air supply or exhaust may be blocked, low gas pressure, or condensate drain clogged.

Applies to: Noritz EZ111/EZ98/EZ71 and NRCR111/NRCR92

Likely causes

  • Clogged air supply (indoor air) or exhaust
  • Low gas supply pressure
  • Clogged or frozen condensate drain line

Test and repair steps

  1. Check the air supply opening and exhaust vent for blockage.
  2. Check inlet gas pressure (NG 3.5-10.5 in. WC, LP 8-14 in. WC).
  3. Check the condensate line for clogs or ice.
  4. Follow the code 90 steps for MM31/MM32 checks and fan/venturi cleaning.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Noritz EZ/NRCR Owner's Guide (Rev. 10-25), Checking for error conditions, p.31. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.