29 Condensate collector water level abnormal

Medium severity Noritz NRC/NRCP

What the control is telling you

Condensate is backing up in the condensate collector of a non-premix condensing unit (NRC/NRCP). The deck only covers the drain line routing.

Applies to: Noritz NRC/NRCP and older non-premix condensing units

Likely causes

  • Drain line smaller than 1/2 in., too long or with flat horizontal runs
  • Drain line pitched up after a horizontal section, or a trap formed in the line
  • Valves added to the drain line, or no air gap at the end
  • Blocked or frozen drain line or failed condensate pump

Test and repair steps

  1. Check the condensate line at least 1/2 in., short and direct.
  2. Any horizontal run must slope down away from the unit (1/4 in. per foot); never pitch it back up.
  3. Remove any valves from the drain line and make sure the end has an air gap.
  4. If a condensate pump is used, check the pump and its 3/8 in. ID tubing.
  5. Clear blockages or ice from the line and confirm condensate flows.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Noritz Residential Level 2 Maintenance & Troubleshooting (NRC/NRCP and older, R2 V1), 29 error code, p.8. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.