Noritz · Tankless water heater
20 High limit switch tripped
What the control is telling you
The high limit switch on the heat exchanger opened because of overheating. Same meaning on all families.
Applies to: All Noritz residential tankless (EZ, NRCR, NCC199CDV, NRC/NRCP)
Likely causes
- Scale deposits in the heat exchanger
- Poor combustion
- Bad wiring or a failed high limit switch
Test and repair steps
- Descale the heat exchanger and clean the inlet filter; check water hardness.
- Check combustion inlet gas pressure, venting, and a clean fan/venturi and burner on premix units.
- Turn off power and check the high limit switch wiring and connector for damage.
- Check the switch for continuity at room temperature; replace if open.
- Warning: Do not jumper the high limit switch.
Settings for these units
- Indoor clearances (required and recommended) · Noritz NRCR
- Operation panel menu settings and defaults · Noritz EZ, Noritz NRCR
- Water quality limits · Noritz EZ, Noritz NRCR
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Noritz EZ/NRCR/CDV Level 2 Maintenance & Troubleshooting (Premix R2 V2), 16 & 20 error codes, p.14; Noritz Residential Level 2 Maintenance & Troubleshooting (NRC/NRCP and older, R2 V1), 14, 16, 20 error codes, p.8; Noritz NRCR Pro training (NRCR92/NRCR111, Printable V3), Poor water quality issues, p.32. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.