Navien · Tankless water heater
E047 Exhaust thermistor open or shorted
What the control is telling you
The exhaust temperature sensor reads open or short circuit.
Applies to: Navien NPE-A2 (built-in recirculation) and NPE-S2 condensing tankless water heaters: NPE-150S2, NPE-180A2/S2, NPE-210A2/S2, NPE-240A2/S2
Likely causes
- Sensor unplugged or damaged
- Wiring fault
- Failed sensor
Test and repair steps
- Turn off power, check the exhaust sensor connector and wiring for damage or corrosion.
- Compare Status Information > 9. Exhaust Temp with real conditions after restart.
- Reset once with the Back button on the front panel and note whether the code returns.
- Fix given phone Navien Technical Support, 1-800-519-8794.
Settings for these units
- Installation clearances (indoor / outdoor) · Navien NPE-2
- Water quality limits and flushing schedule · Navien NPE-2
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NPE-A2/S2 User's Information Manual (20049624A), 5.2 Understanding Error Codes, p.17. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.