Navien · Tankless water heater
E016 Heat exchanger overheating
What the control is telling you
Water temperature in the heat exchanger went too high.
Applies to: Navien NPE-A2 (built-in recirculation) and NPE-S2 condensing tankless water heaters: NPE-150S2, NPE-180A2/S2, NPE-210A2/S2, NPE-240A2/S2
Likely causes
- Clogged cold water inlet filter
- Scale build-up in the heat exchanger (hard water)
- Low water flow through the unit
Test and repair steps
- Clean the cold water inlet filter (and the recirculation inlet filter on A2 models).
- Flush the heat exchanger with a pump, hoses and descaling solution through the isolation valves for at least 45 minutes, then rinse 5 minutes.
- Check water hardness above 7 grains/gal a softener or Navien PeakFlow is recommended, above 12 grains/gal it is required.
- If an external recirculation pump is used, make sure it gives 2-4 GPM through the heater (not more than 4 GPM).
- Reset once with the Back button on the front panel and note whether the code returns.
- Code back after a reset? Stay at the unit and phone Navien Technical Support, 1-800-519-8794.
Settings for these units
- Installation clearances (indoor / outdoor) · Navien NPE-2
- Water quality limits and flushing schedule · Navien NPE-2
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NPE-A2/S2 User's Information Manual (20049624A), 5.2 Understanding Error Codes, p.17. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.