Navien · Tankless water heater

E012 Flame loss

High severity Navien NPE-2

What the control is telling you

The flame went out during operation.

Applies to: Navien NPE-A2 (built-in recirculation) and NPE-S2 condensing tankless water heaters: NPE-150S2, NPE-180A2/S2, NPE-210A2/S2, NPE-240A2/S2

Likely causes

  • Dirty air intake filter
  • Poor electrical ground
  • Low or dropping gas pressure under load
  • Blocked intake/exhaust

Test and repair steps

  1. Clean the air intake filter (top left inside the cabinet, held by one screw); the manual suggests cleaning it every 3-4 months.
  2. Make sure the power cord is properly grounded.
  3. Measure inlet gas pressure at max fire 3.5-10.5 in. WC natural gas, 8.0-13 in. WC propane; look for a large drop when other appliances run.
  4. Inspect intake and exhaust terminations for blockage, snow or ice.
  5. Check Installer Menu > 1. Service Status Info > Flam Loss count to see how often it happens.
  6. Reset once with the Back button on the front panel and note whether the code returns.
  7. Code back after a reset? Stay at the unit and phone Navien Technical Support, 1-800-519-8794.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NPE-A2/S2 User's Information Manual (20049624A), 5.2 Understanding Error Codes, p.17. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.