Navien · Combi boiler

E434 Water adjustment (flow control) valve fault

Medium severity Navien NCB-HNavien NFC-H

What the control is telling you

The DHW flow control (water adjustment) valve is not responding correctly. NFC-H manual lists the reset type as: Alarm.

Applies to: Navien fire-tube combi boilers, NFC-H series (NFC-250/200H, NFC-250/175H) and NCB-H combi boilers (NCB-250/150H, NCB-240/130H, NCB-240/110H, NCB-190/080H, NCB-190/060H)

Likely causes

  • Valve wiring
  • Seized or failed valve

Test and repair steps

  1. Run Test Mode > 10. Flow Control Valve Output; it should travel fully open (0%) to fully closed (100%) and show FEEDBACK.
  2. Check Status Information > 22. Flow control valve status.
  3. Check the valve connector and wiring.
  4. Code keeps returning? Phone Navien Technical Support, 1-800-519-8794.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NCB-H Installation & Operation Manual, 11.7 Understanding Error Codes, p.129-130; Navien NFC-H Installation Manual, 11.7 Understanding Error Codes, p.127-128. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.