Napoleon gas fireplace error codes

1 codes with causes and test steps, plus 2 settings tables.

CodeMeaningSeverity
NO PILOTPilot outMedium

Settings and specs

Framing and combustible clearances

Clearances · Napoleon GD70 STARfire

ItemClearance / size
Framing to stand-offs (top, rear, sides)0 in.
Finishing material to sides of unit3 in.
Finishing material to top of unit7 1/4 in.
Objects in front of fireplace48 in. from front face
Vent pipe to combustibles1 in.
Wall opening for horizontal vent11 1/2 in. min. square or round
Ceiling/roof opening for vertical vent9 1/2 in.
Non-combustible facing over front (GD425 kit)3/4 in. max. thickness
Gas flex connector (Massachusetts)36 in. max. length
  • Hearth extension not required; raise unit to finished floor height so the lower door and trim clear.
  • Non-combustible finish can be skipped if the optional 6 in. bevelled trim is used.
  • Vent must be supported about every 3 ft with 1 in. clearance kept to combustibles.

Source: Napoleon GD70NT-S / GD70PT-S installation & operating instructions W415-0434/C, Installation pp.4, 11, 14; Framing p.15

Combustible mantel height by mantel depth

Clearances · Napoleon GD70 STARfire

Mantel depthMin. height shown in Fig. 37
3 in.3 in. (+ 7 1/4 in.)
4 in.4 in.
6 in.6 in.
7 in.7 in.
  • Fig. 37 marks a 16 in. dimension from the top of the unit to the combustible enclosure top.
  • Drawing is small and the reference point for each height is not clear (top of unit vs. top of the 7 1/4 in. non-combustible finish) - confirm with the mantel graph in the manual before building.

Source: Napoleon GD70NT-S / GD70PT-S installation & operating instructions W415-0434/C, Mantle clearances Fig.37 p.15

Models covered

GD70NT-SGD70PT-S

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.