Lennox · Air conditioner

E427 Inverter DC peak fault (inverter code 21)

High severity

What the control is telling you

DC peak current of 55 A or higher detected; compressor and fan stop. 10 times in an hour = lockout. Inverter LED flash code 21 (red 2 flashes, green 1 flash). S30/S40 thermostat alert code 427 (shown as E427 on the unit control display).

Applies to: Lennox communicating air conditioners incl. variable-capacity inverter units in S30/S40 smart thermostat systems

Likely causes

  • Compressor current spike at restart
  • Older inverter software (XP20/XP25 at defrost entry/exit)

Test and repair steps

  1. XP20/XP25 built before serial number 5817F with frequent 427: compare the inverter part number with the latest in repair parts and replace if needed (newer software has current slope logic).
  2. Serial format PPYYMNNNNN YY and M are year and month built.
  3. Refer to the unit service manual.
  4. Clear by disconnecting and reconnecting power to the outdoor control.
  5. Check inverter LEDs flash code 21 = red 2 flashes, green 1 flash. Normal inverter LEDs with no fault: red ON, green OFF.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.33. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.