Lennox · Air conditioner
E422 Compressor top cap switch open
What the control is telling you
Compressor top cap thermal switch exceeded its limit. S30/S40 thermostat alert code 422 (shown as E422 on the unit control display).
Applies to: Lennox communicating air conditioners incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- Condenser fan, TXV or indoor blower problem
- Stuck reversing valve or clogged filter drier
- Loose top cap switch wire (XC/XP25)
Test and repair steps
- Check condenser fan motor, TXV and indoor blower.
- Check for a stuck reversing valve or clogged refrigerant filter.
- XC/XP25 make sure both top cap switch wires are on the TP terminals of the outdoor control.
- Check superheat and subcooling.
- Clears when corrected.
Settings for these units
- Outdoor unit clearances · Lennox EL16KC1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.32. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.