Lennox · Air conditioner

E417 Discharge sensor faulty

Medium severity

What the control is telling you

Discharge line temperature sensor open, shorted or out of range (checked after 90 seconds). Escalates after 10 minutes. S30/S40 thermostat alert code 417 (shown as E417 on the unit control display).

Applies to: Lennox communicating air conditioners incl. variable-capacity inverter units in S30/S40 smart thermostat systems

Likely causes

  • Failed sensor
  • Sensor leads in the wrong pins of the harness connector

Test and repair steps

  1. Check sensor resistance against the temperature/resistance chart in the unit instructions; replace if out of range.
  2. Verify harness pin positions against the unit's terminal table; order a replacement cable assembly if the pins are wrong.
  3. Critical condition power down, replace sensor or cable, power up to clear.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.31. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.