ICP · Furnace
6 Ignition proving failure
What the control is telling you
No flame sensed during trial for ignition. Control retries 3 more times before 6+1 lockout. If flame is lost during blower on-delay, blower runs for the off-delay.
Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)
Likely causes
- Gas turned off at valve or manual shut-off
- GREEN/YELLOW ground wire not connected to sheet metal
- Flame sensor grounded, dirty or faulty
- Igniter or igniter harness failure
- No 24 V to gas valve / valve not opening
- Low inlet gas pressure, poor carryover, rough ignition, wrong firing rate, air leak around igniter bracket
Test and repair steps
- Check manual gas shut-off and gas valve switch are ON.
- Make sure the GREEN/YELLOW wire is connected to furnace sheet metal and the flame sensor is not grounded.
- Run component test remove R, reset power, SW1-6 ON. Igniter must glow orange/white within the 15-second warm-up. If not, check 115 V between pin 3 and NEUTRAL-L2 for 15 s: present = check harness/igniter (cold 40-70 ohms), absent = replace control.
- Reconnect R, call for heat check 24 V at gas valve BLUE and GREEN/YELLOW wires; no 24 V = check connections, then replace control; 24 V but no gas = check all valves on, replace valve.
- Check flame current during trial for ignition: below 0.5 DC microamps = clean sensor with fine steel wool; nominal is 4.0-6.0 microamps; replace sensor if still low.
- If burners drop out only at low fire, test at maximum heat, check manifold pressure, burner carryover and sensor position.
- Check inlet gas pressure 4.5-13.6 in. w.c. (natural gas) and air leaks around the igniter bracket.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Figure 16 Troubleshooting Chart, p.34. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.