4+2 Inducer motor fault
What the control is telling you
Inducer did not start within 20 seconds of a heat call, its RPM is out of range, or the RPM signal was lost for 5 seconds while running.
Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)
Likely causes
- Wrong vent sizing
- Failed inducer motor
- Restricted combustion air supply
- Improper inducer motor wiring
Test and repair steps
- Check vent and combustion air piping for size and obstructions.
- Check inducer motor wiring and connectors at the control.
- Run component self-test (SW1-6) - inducer should run at medium speed.
- Replace the inducer motor if it does not run or its speed signal is missing.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Figure 16 Troubleshooting Chart, p.35. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.