4+1 Blower motor fault

High severity ICP (F/G)9MAE Modulating Furnace

What the control is telling you

Blower did not reach 250 RPM or failed to communicate: within 30 seconds of start, or within 10 seconds during steady running.

Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)

Likely causes

  • Rubbing or loose blower wheel
  • Open wire / bad terminal between control and motor (BLACK/WHITE, RED/GREEN, YELLOW, BLUE)
  • Failed blower control module
  • Failed furnace control

Test and repair steps

  1. Warning: Turn power off before working on the blower.
  2. Remove R from the control, unplug PL13 and PL14 at the motor; check the wheel spins freely - if not, fix the wheel/motor.
  3. Power on check 115 VAC at PL14-5 to PL14-4; if missing, find the open BLACK or WHITE lead (disconnect power choke if fitted and check continuity).
  4. Check 12 VDC at PL13-1 RED(+) to PL13-4 GREEN(-); if missing check PL3-1 to PL3-2 at the control - missing there = replace control, present there = open RED/GREEN wire.
  5. Check 5 VDC at PL13-2 YELLOW(+) to PL13-4 GREEN(-); if missing, check PL3-3 to PL3-2 at control - missing = replace control, present = open YELLOW wire. Reading must be stable within 0.02 VDC.
  6. With PL13/PL14 unplugged, check PL13-3 BLUE(+) to PL13-4: near 0 VDC with brief pulses several times a second; if no pulses, check PL3-4 to PL3-2 at control (no pulses = replace control, pulses = open BLUE wire).
  7. Reconnect motor; if PL3-3 YELLOW voltage fluctuates more than before, replace the blower control module (check whether the whole motor needs replacing); otherwise replace the furnace control.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Figure 16 Troubleshooting Chart, p.35. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.