Goodman · Furnace
EE0 Lockout - too many ignition retries (3)
What the control is telling you
The control tried to light the burners 3 times and failed (no flame proven, or flame lost after lighting), so it locked out. The flowcharts call this code E0.
Applies to: Goodman/Amana/GMC gas furnaces, 9-speed ECM, 7-segment control. Two-stage 96%: AC9C96, AM9C96, GC9C96, GM9C96. Single stage 80%: VC9S80, VM9S80, AC9S80, AM9S80, GC9S80, GM9S80. Single stage 92/96%: VC9S96, VM9S96, AC9S96, AM9S96, AM9S92, GC9S96, GM9S96, GM9S92
Likely causes
- Gas supply off or interrupted, gas valve switch OFF, or low inlet/manifold pressure
- Hot surface igniter not glowing, cracked or out of position
- Dirty or oxidized flame sensor / weak flame signal
- Vent or intake pipe blocked, too long, too many elbows or wrong termination; weak inducer
- 90% models: front cover (coil cover) pressure switch opening because the condensate trap or drain is blocked or not primed
- Poor ground or reversed line polarity (control cannot sense flame)
Test and repair steps
- Read the active code (Err menu) and the fault history (L6F menu) on the 7-segment display; cycle the thermostat to retry and watch the full sequence.
- Confirm the inducer starts and the igniter glows for the whole warm-up. No glow: check for 115 VAC at the igniter during warm-up - if voltage is there, replace the igniter.
- Igniter check (power off, igniter at 70-77 F): silicon nitride igniter should read 37-68 ohms. 80% models with the carbide mini igniter: 30-300 ohms.
- If the burners do not light gas valve switch ON, 24 VAC at the valve during trial for ignition, inlet pressure 4.5-10.0 in. w.c. natural gas / 11.0-13.0 in. w.c. LP with all appliances running.
- Check manifold pressure while firing natural gas high fire 3.2-3.8 in. w.c., LP 9.7-10.3 in. w.c. (see the Gas pressure table for each model).
- 90% models: make sure the front cover pressure switch stays closed - prime and clear the drain trap, check the switch hose for kinks or water, and check vent length, elbows and termination.
- If the burners light then drop out measure flame current with a DC microamp meter in series with the sensor - normal is 1 to 4 microamps. Clean the sensor with steel wool and check its position in the flame.
- Check grounding and polarity a reversed hot/neutral or a high-resistance neutral can cause flame-sense lockouts.
- Make sure manifold pressure stays steady during the run and does not drop below the range.
Settings for these units
- Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
- Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman RS6612022r1 (GM9S92/GM9S96/GC9S96 service), 1 Stage Troubleshooting Codes, p.29-30; Goodman RS6621008r2 (GM9S80 service), p.32-33; Goodman RS6612020r1 (GM9C96 service), 2 Stage Troubleshooting Codes, p.35-36; Error Codes (E0) flowchart p.51 (RS6612022r1), p.36 (RS6621008r2), p.39 (RS6612020r1); Checking Hot Surface Ignitor / Flame Sensor p.24-26. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.