Goodman · Furnace

E11 Flame rollout switch open

Critical severity Goodman/Amana GM9S96/AM9S96Goodman/Amana GM9S80/AM9S80Goodman/Amana GM9C96/AM9C96

What the control is telling you

A manual-reset flame rollout switch on the burner/manifold area has opened - flame came out of the burner box. The circulator blower runs continuously and the furnace will not fire.

Applies to: Goodman/Amana/GMC gas furnaces, 9-speed ECM, 7-segment control. Two-stage 96%: AC9C96, AM9C96, GC9C96, GM9C96. Single stage 80%: VC9S80, VM9S80, AC9S80, AM9S80, GC9S80, GM9S80. Single stage 92/96%: VC9S96, VM9S96, AC9S96, AM9S96, AM9S92, GC9S96, GM9S96, GM9S92

Likely causes

  • Wrong gas pressure / overfiring or wrong orifices
  • Burners misaligned or restricted; orifice plate out of position
  • Flame impingement, burners with oversized cross-over slots
  • Air leaking around or through the heat exchanger (possible cracked heat exchanger)
  • Blocked flue

Test and repair steps

  1. Warning: a rollout trip means flame left the burner box - find the cause before putting the furnace back in service.
  2. Remove the burner door, press the reset on the rollout switch and check it for continuity with an ohmmeter; replace it if it will not stay closed.
  3. Check inlet and manifold gas pressure against the rating plate and the orifice size.
  4. Check burner alignment, the orifice/heat exchanger plate position and look for burner or flue restriction.
  5. Inspect the heat exchanger for leaks; check for air leaking into the burner compartment.
  6. Run a full heat cycle and watch the flame pattern before leaving.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman RS6612022r1 (GM9S92/GM9S96/GC9S96 service), 1 Stage Troubleshooting Codes, p.29-30; Goodman RS6621008r2 (GM9S80 service), p.32-33; Goodman RS6612020r1 (GM9C96 service), 2 Stage Troubleshooting Codes, p.35-36; Checking Flame Rollout Control p.20 (RS6612022r1), p.27 (RS6612020r1). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.