Daikin · Furnace

EEE Internal control fault (IRQ loss)

High severity Daikin DR96TN/DD96TN

What the control is telling you

The integrated control board found an internal fault. The furnace will not operate.

Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready

Likely causes

  • Integrated control board failure
  • Electrical noise or power disturbance

Test and repair steps

  1. Cycle power to the furnace and check whether the code returns.
  2. Check supply voltage (115 V +/- 10%) and grounding.
  3. If the code returns, replace the integrated control board.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.