Daikin · Furnace

EEC Internal gas valve error - valve energized when it should not be

Critical severity Daikin DR96TN/DD96TN

What the control is telling you

The control sees voltage at the gas valve with no call for heat. Flowcharts call this code EC. Note: the wiring diagram legend labels this code 'External Gas Valve Error' while the troubleshooting chart and flowchart say internal - follow the chart.

Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready

Likely causes

  • Gas valve relay on the control board stuck closed
  • Miswiring that feeds the gas valve circuit
  • Gas valve shorted to ground or loose connection

Test and repair steps

  1. Warning: a valve powered with no call for heat is a safety hazard - shut off the manual gas valve until repaired.
  2. Check the gas valve wiring for miswiring and correct it.
  3. With no call for heat, check for voltage at the gas valve. Voltage present = board relay stuck closed; replace the integrated control board.
  4. Remove the valve wires and check them for voltage; if present, check the valve for a short to ground or loose connection and repair or replace the valve.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29; Error Code (Eb & EC) flowchart p.37; wiring diagram legend p.38. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.